Strut Services Group, Inc.

Unistrut Alabama

P2484

$

P2484 – 7 Hole, 90° Gusseted Fitting

Part No. Finish Product Weight / Piece (lbs)
P2484 EG 1.34
P2484 DF 1.41
P2484 HG 1.41
P2484 GR 1.34

Standard Dimensions (Unless Shown Otherwise on Drawing):

  • Hole Diameter: 9/16″ (14mm)
  • Hole Spacing (From End): 13/16″ (21mm)
  • Hole Spacing (On-Center): 1 7/8″ (48mm)
  • Width: 1 5/8″ (41mm)
  •  Thickness:
    • 1/4″ (6.4mm) with steel meeting or exceeding ASTM A1011 SS GR 33, or
    • 0.220″ (5.6mm) with steel meeting or exceeding ASTM A1011 HSLAS GR 45

Note:

When used for mechanical supports, load capacities of brackets and fittings should be in compliance with the American Standard Code for Pressure Piping.

Materials & Finishes – Standard:

  • Base Metal: Steel conforms to ASTM A1011 SS GR 33, A1011 HSLAS GR 45, A36, A575, A576, or A635.
  • Electrogalvanized (EG):  Conforms to ASTM B633, Type III SC1
  • Unistrut Defender (DF):  Conforms to ASTM A1059
  • Hot Dip Galvanized (HG):  Conforms to ASTM A123 or A153
  • Perma-Green (GR):  Conforms to commercial standards for powder coating
  • Perma-Gold (ZD):  Conforms to ASTM B633, Type II SC1 or SC3
  • Plain (PL):  No finish

Materials & Finishes – Special Metals:

  • Stainless Steel, Type 304 (SS):  Conforms to ASTM A240 or A276, Type 304 *
  • Stainless Steel, Type 316 (ST):  Conforms to ASTM A240 or A276, Type 316 *
  • Aluminum (AL):  Conforms to ASTM B209, Type 1100F or 5052-H32 *

* These materials have different physical properties and performance characteristics. Please contact us for design support.

 

<!–

–>

Design Loads – P2484 & P2484W (Bending Moment)
Beam Loading – P1001
Part Number Load Case  Minimum Ultimate Load
(lbs)
Moment (in-lbs) Average Deflection at Design Moment
Min. Ultimate
Span/360
(lbs)
P2484 A 1,030 10,300 3,400 0.126″
B 3,400 34,000 11,300 0.149″
P2484W A 1,150 11,500 3,800 0.112″
B 4,800 48,000 16,000 0.180″

 

Notes:

Design Loads only apply to UNISTRUT brand products. Look for “UNISTRUT” on the part.
Safety Factor = 3.0 based on static testing to the ultimate strength of connection.
Two (2) 1/2″ Unistrut Channel Nuts and Cap Screws torqued to 50 ft-lbs required for installation.
Bolts can be located in any 2 of the 3 leg holes.